Arc resistant switchgear lineup with vent path
Arc Resistant Switchgear · IEEE C37.20.7 · Fort Myers, FL

Arc resistant switchgear,Built to the test report, not the marketing

Type 2B arc resistant LV and MV switchgear tested to IEEE C37.20.7. Fast bus protection, optical arc flash detection, and zone-selective interlocking integrated by default. Documented end to end for the AHJ and your insurance carrier.

Type-tested standard
IEEE C37.20.7
Front, sides, rear
Type 2B
480V through 15kV
LV & MV
Bus protection trip
Cycle-fast

Why It Matters

Arc resistance is a tested rating, not a feature you can claim.

A rating earned by testing, not by claim

Arc resistant switchgear is a type-tested rating under IEEE C37.20.7. Type testing means a sample lineup, in the exact configuration, was subjected to an actual internal arcing fault and met the criteria for personnel protection. A label without the test report behind it is marketing, not protection.

Engineered to preserve the rating

Most of the field failures we see in arc resistant switchgear come from modifications that quietly invalidated the rating: a different breaker, a different relay, a venting path that was field-modified. Every lineup we engineer is built to keep the type-tested configuration intact, end to end.

Fast clearing reduces the energy at the source

Arc-resistant construction contains and vents the fault. Fast clearing keeps it from getting bigger in the first place. We integrate optical arc flash detection, zone-selective interlocking, and fast bus protection to clear the fault in a single cycle where applicable.

Documented for the next 30 years

Type test reports, qualifying documentation, IEEE C37.20.7 compliance basis, arc flash study, NFPA 70E labels, and the as-built drawings. Everything the AHJ, your insurance carrier, and the next engineer will ask for.

Accessibility Types

Which surfaces and conditions the rating actually covers.

Type 1

Front only

Personnel protection on the front of the lineup with the doors closed and latched. Common for installations with restricted access on the sides and rear.
Type 2

Front, sides, rear

Personnel protection on all enclosed sides with the doors closed and latched. The common rating for most modern arc resistant installations.
Type 2B

Type 2 + low-voltage compartment

Type 2 protection with the low-voltage instrument compartment door open for routine relay and metering access. The most common rating we engineer to because it reflects how operators actually work on the gear.
Type 2C

Type 2 + adjacent compartments

Type 2 protection between adjacent compartments inside the lineup. Required for installations where a single fault should not propagate to neighboring breaker cells.

What Goes Into the Design

Six engineered elements every arc resistant lineup includes.

Pressure-relief venting

Engineered plenums and ducts route fault pressure away from the operator-facing surfaces. The path is part of the type-tested configuration, not field-improvised.

Reinforced enclosure

Doors, panels, and structural elements designed and verified to withstand the dynamic pressure of an internal arcing fault without door blowout or panel detachment.

Optical arc flash detection

Light-sensing arc flash relays inside the compartments detect ignition in under a millisecond and trip the upstream breaker in a single cycle. Coordinated with the bus protection.

Zone-selective interlocking and fast bus protection

Coordination logic that lets the breaker closest to the fault clear first, fast, without waiting for time-graded coordination. Reduces incident energy by an order of magnitude.

Vent path and stack design

For indoor installations, the venting path runs into a plenum, a chase, or an outdoor stack. Part of the engineering package, not an installer afterthought.

Remote racking and switching

Operators perform racking and switching from outside the arc flash boundary using remote racking devices and wireless controls. Reduces personnel exposure even further.

Specifications

The technical envelope.

Standard
IEEE C37.20.7 Guide for Testing Metal-Enclosed Switchgear for Internal Arcing Faults
Voltage class
Low voltage 208V through 600V; medium voltage 4.16kV through 15kV class
Accessibility ratings
Type 1, Type 2, Type 2B, Type 2C; configured to the application
Arcing fault current
Type tested to the rated short-time current of the lineup
Arc duration
0.5 seconds typical for the type test; coordinated with the protection scheme to clear faster in service
Fast protection
Optical arc flash detection, zone-selective interlocking, fast bus protection, configurable per application
LV breakers
Drawout low voltage power circuit breakers (UL 1066) in UL 1558 listed assemblies
MV breakers
Vacuum interrupters in IEEE C37.20.2 metal-clad assemblies
Documentation
Type test report, qualifying configuration documentation, arc flash study, NFPA 70E labels, PE-stamped engineering

The Retrofit Question

Modifying arc resistant switchgear is harder than modifying anything else.

Most failures we encounter come from modifications that quietly invalidated the rating. Here is how we keep that from happening.

Modification invalidates the rating

Any change to the type-tested configuration (different breaker, different trip unit, different vent path) means the lineup is no longer running the configuration that was tested. The rating is invalidated until the new configuration is revalidated.

Revalidation is engineering, not paperwork

Revalidating a modified arc resistant lineup either requires a new type test on the modified configuration, or engineering analysis demonstrating equivalence to the original test. We do both, depending on the scope of the change.

Fast protection retrofit

Many lineups can be improved by adding optical arc flash detection, zone-selective interlocking, or fast bus protection without modifying the structural configuration. We retrofit the protection layer to reduce incident energy without affecting the type-tested rating.

Documentation reconstruction

For older arc resistant lineups where the original type test documentation has been lost, we work with the OEM (where available) or perform the engineering analysis required to rebuild the qualification basis. Without that, the rating is not provable.

How It Works

From application review to documented commissioning.

  1. 01

    Application review

    Accessibility requirement (Type 1, 2, 2B, 2C), voltage class, fault current, and operator workflow. Sized for what the operators actually do, not the spec template.

  2. 02

    Engineering and qualification

    PE-stamped engineering package, IEEE C37.20.7 qualification basis, arc flash study, NFPA 70E labels, and the documentation the AHJ will ask for.

  3. 03

    Build, test, install

    Factory build of the type-tested configuration, witnessed acceptance test on request, then field install and commissioning.

  4. 04

    Commission and document

    Full functional test, arc flash labels installed at energization, operator training, and the complete documentation handoff. ControlCom Connect activated.

In the Field

What an arc resistant lineup looks like installed.

Who It Is For

Built for the places personnel work on energized gear.

  • Healthcare

    Hospital service entrance, surgical suite distribution, and essential electrical systems where operator safety is non-negotiable.

  • Data Centers

    Critical distribution where remote racking, fast clearing, and personnel protection are required for concurrent maintainability.

  • Utilities & Generation

    Substations, generation plants, and switchyards where worker safety on energized gear is a daily operational requirement.

  • Industrial & Process

    Plants where operator exposure during routine racking, testing, and maintenance has to stay inside Cat 2 PPE without restriction.

Common Questions

Answers from our engineering team.

Talk to a Power Systems Engineer

Tell us the accessibility type you need, the voltage class, the fault current, and whether this is new or a retrofit. We will get back within 24 hours.

  • Reviewed by a power systems engineer, not a salesperson
  • IEEE C37.20.7 qualification documentation included
  • Arc flash study and NFPA 70E labels at energization
  • Vendor-neutral, fully documented, ControlCom Connect ready

Tell us about your arc resistant project

Accessibility type, voltage class, fault current, and whether it is new or a retrofit.