
Type 2B arc resistant LV and MV switchgear tested to IEEE C37.20.7. Fast bus protection, optical arc flash detection, and zone-selective interlocking integrated by default. Documented end to end for the AHJ and your insurance carrier.
Why It Matters
Arc resistant switchgear is a type-tested rating under IEEE C37.20.7. Type testing means a sample lineup, in the exact configuration, was subjected to an actual internal arcing fault and met the criteria for personnel protection. A label without the test report behind it is marketing, not protection.
Most of the field failures we see in arc resistant switchgear come from modifications that quietly invalidated the rating: a different breaker, a different relay, a venting path that was field-modified. Every lineup we engineer is built to keep the type-tested configuration intact, end to end.
Arc-resistant construction contains and vents the fault. Fast clearing keeps it from getting bigger in the first place. We integrate optical arc flash detection, zone-selective interlocking, and fast bus protection to clear the fault in a single cycle where applicable.
Type test reports, qualifying documentation, IEEE C37.20.7 compliance basis, arc flash study, NFPA 70E labels, and the as-built drawings. Everything the AHJ, your insurance carrier, and the next engineer will ask for.
Accessibility Types
Front only
Front, sides, rear
Type 2 + low-voltage compartment
Type 2 + adjacent compartments
What Goes Into the Design
Engineered plenums and ducts route fault pressure away from the operator-facing surfaces. The path is part of the type-tested configuration, not field-improvised.
Doors, panels, and structural elements designed and verified to withstand the dynamic pressure of an internal arcing fault without door blowout or panel detachment.
Light-sensing arc flash relays inside the compartments detect ignition in under a millisecond and trip the upstream breaker in a single cycle. Coordinated with the bus protection.
Coordination logic that lets the breaker closest to the fault clear first, fast, without waiting for time-graded coordination. Reduces incident energy by an order of magnitude.
For indoor installations, the venting path runs into a plenum, a chase, or an outdoor stack. Part of the engineering package, not an installer afterthought.
Operators perform racking and switching from outside the arc flash boundary using remote racking devices and wireless controls. Reduces personnel exposure even further.
Specifications
The Retrofit Question
Most failures we encounter come from modifications that quietly invalidated the rating. Here is how we keep that from happening.
Any change to the type-tested configuration (different breaker, different trip unit, different vent path) means the lineup is no longer running the configuration that was tested. The rating is invalidated until the new configuration is revalidated.
Revalidating a modified arc resistant lineup either requires a new type test on the modified configuration, or engineering analysis demonstrating equivalence to the original test. We do both, depending on the scope of the change.
Many lineups can be improved by adding optical arc flash detection, zone-selective interlocking, or fast bus protection without modifying the structural configuration. We retrofit the protection layer to reduce incident energy without affecting the type-tested rating.
For older arc resistant lineups where the original type test documentation has been lost, we work with the OEM (where available) or perform the engineering analysis required to rebuild the qualification basis. Without that, the rating is not provable.
How It Works
Accessibility requirement (Type 1, 2, 2B, 2C), voltage class, fault current, and operator workflow. Sized for what the operators actually do, not the spec template.
PE-stamped engineering package, IEEE C37.20.7 qualification basis, arc flash study, NFPA 70E labels, and the documentation the AHJ will ask for.
Factory build of the type-tested configuration, witnessed acceptance test on request, then field install and commissioning.
Full functional test, arc flash labels installed at energization, operator training, and the complete documentation handoff. ControlCom Connect activated.
In the Field
Arc resistant switchgear lineup with the venting plenum routed up and out, optical arc flash relays visible in the low voltage compartment, and IEEE C37.20.7 Type 2B labeling on the cabinet
1920 × 1080 (16:9)
Who It Is For
Hospital service entrance, surgical suite distribution, and essential electrical systems where operator safety is non-negotiable.
Critical distribution where remote racking, fast clearing, and personnel protection are required for concurrent maintainability.
Substations, generation plants, and switchyards where worker safety on energized gear is a daily operational requirement.
Plants where operator exposure during routine racking, testing, and maintenance has to stay inside Cat 2 PPE without restriction.
Related
UL 1558 platform that the LV arc resistant lineups are built on.
Multi-generator paralleling, often specified arc resistant.
Engineered to your single-line, fault current, and operating modes.
Standards (IEEE C37.59 and C37.20.7), arc flash, and what zero-downtime really means.
Zero-downtime modernization with arc-resistant rating preserved.
Common Questions
Tell us the accessibility type you need, the voltage class, the fault current, and whether this is new or a retrofit. We will get back within 24 hours.
Accessibility type, voltage class, fault current, and whether it is new or a retrofit.